Single phase, 2 wire.
50Hz ± 3Hz.
AC 100V rms to 270V rms.
> 75% at 230V AC input and Fully loaded.
Equipment supply - 5V at 2.0 Amps max. Battery supply - 13.8V at 1.0A ± 0.20A max.Battery is to be directly floated across the load, however it has separate terminals. Battery is connected to the load through a fuse and reverse polarity protection circuit.
Load output (with battery disconnected) will be regulated with in ±2%, with battery connected will follow the battery voltage.
Ripple on output load terminal (with battery disconnected) will be less than 150mV.
Noise will be less than 300mV Pk - Pk.
Battery charging will take place with constant voltage, constant current Maximum charging current of the battery is limited to 1.0A ± 0.20A.
Maximum Charging Voltage is Set at 13.8V ± 2%.
Available
Available
Will be ON when AC is available.
Will be ON when Battery is supplying power to the Equipment.
Will be ON when Battery voltage is below 10.30V to 10.80V.
Free air convection cooling.
Operation -5 to +50 ºC
Storage -5 to +60 ºC
Operating 5% RH to 85% RH non - condensing
Storage 5% RH to 95% RH non - condensing
1.5 KV AC rms at 50Hz for one minute ( trip current set at 5mA).
1) Between INPUT and CHASIS.
To be less than 200mW with a test current of 2.0A through GND
W = 111.5mm H = 47mm D = 110mm.
Approx 0.5 kgs.