This specification defines the performance characteristics of SMPS based 300Wmax., Float to Boost Charger Power Supply.
170VAC - 270VAC
50Hz ± 3Hz
< 20A peak @ 230VAC,cold start @ 25º C.
< 3.0A rms @ 170VAC and output full load
> 80% under all line conditions and full load.
13.70VDC ± 0.50V
14.70VDC ± 0.50V
20 .0Amp, ± 0.5A
< 200mV. Pk - Pk, at Nominal Input
< 400mV. Pk - Pk, at Nominal Input (measured with 0.1μF ceramic disc & 10μF Electrolytic capacitor across output in 20 MHz bandwidth oscilloscope.)
Ripple on the outputs ( with battery disconnected ) shall be less than 1%, & Noise less than 2%
< 20.50Amp at all AC Input Conditions
3Amp - 5Amp current
When ever discharged battery is connected to charger the output voltage goes to boost charging mode and will start charging the Battery. Once Battery is fully Charged the output voltage will change from boost to float mode and maintains the battery in fully charged Condition.
The Power Supply is fully protected against over load & short ckt. During over load output fold back and resumes to normal operation on removal of over loads. During short circuit at output the Power Supply will go in to hick up mode and resumes normal operation on Removal of the short circuit.
Once Battery is fully Charged the protection circuit changes from Boost mode to Float mode and it does not allow further charging. During charging time when ever the battery charging current reduces to 4.0A ± 1.0A the output will change from boost to float mode.
On Battery reversal, 30A fuse mounted on the PCB will blow, The Power Supply is isolating from the Battery.
Operation Ambient 0ºC to + 50ºC ambient. Storage 0ºC to + 75ºC ambient.
Operating 5% RH to 95% RH non-condensing. Storage 5% RH to 95% RH non-condensing.
Tested at 3.0KVAC rms at 50Hz for 60 Sec. with a trip current of 5mA.
1. Between INPUT and OUTPUT.
When tested with a 500VDC Megger shall not be < 20 Mega Ohms Between Shorted INPUT and Shorted OUTPUT Terminals.
Designed to meet CISPR22 CLASS-A
25,000 hours at full load and 25ºC ambient conditions.
GREEN LED is provided to indicates mains ON & Battery is fully Charged.
RED LED is provided to indicate battery charging.
The Power Supply is protected against over temperature. In case of over temperature the Power Supply output gradually reduced, O/P Power limits & recovers normal operation automatically when the temperature reduces.
0 to 20V analog voltmeter provided on the front panel to read the Load and battery voltage.
0 to 25A analog ammeter provided on the front panel to read the Load and battery currents.
Forced air cooling.
A transulant polythene cover of suitable dimension.
A white child carton of suitable size.
WIDTH : 242mm , DEPTH : 255mm , HEIGHT : 96mm
3.0 kgs