BM306A

BM306A (13.5V@25A Power Supply cum Battery Charger)

General Specification

  • Scope:

    This specification defines the performance characteristics of a 13.8V, 25A equipment supply cum battery charger operating on Single phase AC supply.

Input Requirements

  • Phase

    Single phase, 2 wire and ground.

  • Input Frequency

    50Hz ± 3Hz

  • Input Voltage

    AC 170V rms to 270V rms.

  • Efficiency

    > 75% at 230V, Full load.

01 Output Characteristics
+

Outputs

The Power Supply has two output terminals i.e., Equipment and the Battery. The Battery is directly floated across the Equipment internally. When battery is connected, the Equipment output terminal Will foll ow the battery voltage.

Output Voltage and Current

Equipment output-13.80V at 25.0 Amps max.(without connect battery) Battery output 13.80V at 10.0 Amps max. (When the wireless set is not In transmit mode). Maximum output power (Equipment + Battery) is Limited to 350W max.

Output Voltage Adjustment

Output Voltage settable from 12.0V to 14.20V DC by adjusting the (V.adj.) potentiometer provided on the front panel.

Battery Charging

Battery charging will take place with constant voltage, constant current. Maximum charging current of the battery will be limited to 10.0A + 20%. Maximum charging voltage to be 14.00V.

Output Voltage Regulations

With the Battery disconnected, output voltage will remain within ± 2% Of the set values. And when battery is connected the output will follow The battery voltage

Ripple & Noise

Ripple on the outputs ( with battery disconnected ) shall be less than1%, & Noise less than 2%.

02Protections
+

Output over Voltage

PSU trips on output over voltage condition (above 15V) and resume to normal operation on removal of fault condition and AC power Re-cycling with 20sec interval between switch OFF and ON.

Output over Load and Short ckt

Output folds back or Hick Up mode on over power or short circuit condition and resume to normal operation on removal of over power or Short circuit condition.

Battery Reverse

On reverse polarity Red LED indication is provided at Battery terminal Connecting side. Charge is protected against the reverse.

Battery Deep Discharge Cut-Off

During power off condition, the battery supply power to the equipment. When the battery voltage falls below 10.80V, a b attery low LED Will turn ON and Buzzer alarm will be provided on continues mode. to protect the battery from damage due to deep discharge the battery is isolated fro m the equipment, when the battery voltage falls below 10.8V After restoration of AC mains, to ensure the availability of required equipment current and safety of the battery, the battery is initially charged with 1.0A current by an auxiliary charger, till the battery voltage reaches11.40V, after which the battery is reconnected to the equipment and normal Charging (10.0A max.) takes place.

03Indications Alrams
+

Mains On

Will be ON when AC is available.

Battery On

Will be ON when the battery is supplying power to the Radio.

Battery Low

Will be ON when the battery voltage is 10.80V ± 0.2V will start.

Battery Reverse

Will be ON when the battery is Reverse Connected.

Battery Low

Buzzer alarm will be provided on continues mode. when the Battery Voltage < 11.40V will start.

04Display Metering
+

Voltmeter

0 to 20V analog voltmeter provided on the front panel to read the Load and battery voltage.

Ammeter

0 to 30A analog ammeter provided on the front panel to read the Load and battery currents.

05Cooling
+

Free air convection.

06 Environment
+

Temperature

Operating 0 to 50ºC.

Humidity

Operating 5% RH to 85% RH non-condensing. Storage 5% RH to 95% RH non-condensing.

07 Product Safety
+

DI-Electric Voltage Withstand Test

Tested at 1.5KV rms AC for one minute with a trip current of 5mA.

a) Between INPUT and CHASSIS.

b) Between INPUT and OUTPUT.

Earth Ground Resistance

To be less than 200m when tested at 10Amp DC current.

08Enclosure
+

Dimensions

WIDTH : 260mm , DEPTH : 290mm , HEIGHT : 104mm

Weight

3.85Kgs.

Copyright © 2025 Axiom Power Products Pvt. Ltd. All Right Reserved. Designed by